Design Loads Methodology
This section provides a breakdown of how each action listed in Design Loads was calculated. Seismic acceleration is taken into account in these actions by:
- Utilising BS EN 1998-5 Annex E (E.2) to calculate a seismic value of Ka (the calculation of dynamic soil pressures is discussed in Earth Pressure — Seismic).
- Multiplying all densities and surcharge magnitudes by (1-kv) to emulate the inertia caused by a downward seismic acceleration in accordance with BS EN 1998-5 Annex E (E.1).
- Including the additional actions of block wall inertia & hydrodynamic effects.
In this section
- Concrete — self-weight and inertia
- Hydrostatics — tidal lag, uplift/downthrust, and horizontal pressure
- Hydrodynamics — landward and seaward hydrodynamic thrust
- Earth Pressure — static and seismic earth pressure
- Surcharge — uniformly distributed, patch, and stacked loads
- Bollard Loading